Input ControlSpecifications | 3 - 32 VDC | ||
Min | Max | Units | |
Input on voltage | 3 | 32 | VDC |
Input off voltage | 1 | VDC | |
Input Current | 12 | 22 | mA |
Reverse voltage protection | 32 | VDC |
Output Specification | |||||
Max Output Current | 10 | 16 | 25 | 40 | A |
Line Voltage | 480 | 480 | 480 | 480 | VAC |
Frequency range | 47 - 63 | 47 - 63 | 47 - 63 | 47 - 63 | Hz |
Max on state voltage drop | 1.5 | 1.5 | 1.5 | 1.5 | VAC |
Peak one cycle surge on state current | 110 | 160 | 250 | 350 | A |
turn-on time | 10 | 10 | 10 | 10 | ms |
Random turn on time max. | 50 | 50 | 50 | 50 | μs |
urn off time | 10 | 10 | 10 | 10 | ms |
Off state leakage max at 440 VAC | 10 | 10 | 10 | 10 | mA |
All Dimensions are in mm
Input Control Specifications | 80 - 240 VAC | ||
Min | Max | Units | |
Input on voltage | 80 | 240 | VAC |
Input off voltage | 45 | VAC | |
Input Current | 5 | 15 | mA |
Dielectric Strength Input to Output | 2500 | VAC |
Output Specification | |||||
Max Output Current | 10 | 16 | 25 | 40 | A |
Line Voltage | 480 | 480 | 480 | 480 | VAC |
Frequency range | 47 - 63 | 47 - 63 | 47 - 63 | 47 - 63 | Hz |
Max on state voltage drop | 1.5 | 1.5 | 1.5 | 1.5 | VAC |
Peak one cycle surge on state current | 110 | 160 | 250 | 350 | A |
turn-on time | 10 | 10 | 10 | 10 | ms |
Random turn on time max. | 50 | 50 | 50 | 50 | μs |
turn off time | 10 | 10 | 10 | 10 | ms |
Off state leakage max at 440 VAC | 10 | 10 | 10 | 10 | mA |